ContentsGENERAL SAFETY INFORMATION ... 2RECEIVING, MOVING, UNPACKING ... 21.0 INSTALLATION ...
10TROUBLESHOOTING GUIDEC) Checkpoint faults1. Power on/off light2. Compressor on light off3. Alarm/Service alert light on -check Display for activecon
11PARTS LIST208-230/3/60 380-420/3/50, 460/3/60, and 575/3/60 PARTS DESCRIPTION 200 250,300 400,500 750 200 250,300 400,500 750 Condensing Unit (ai
SERVICE DEPARTMENT: (724) 746-1100Devair Inc.Formerly DeVilbiss Air Compressor ProductsP.O. Box 3000 Barrie, Ontario L4M 4V6Tel: (705) 728-5657Warrant
1. PRESSURIZED DEVICES:This equipment is a pressurecontaining device.• Do not exceed maximum operating pressure asshown on equipment serial number tag
333°F...39°F1°C... 4°CIMPORTANT: READ PRIOR TO STARTING THIS EQUIPMENT1.0 INSTALLATION1.1 LocationA. For typical placement in a
41.6 Electronic Demand DrainInstallation1. Remove Service Panel by removing two shippingscrews and turning (2) Quick Release Locks.2. Reach inside and
52.2 Start-upA. Energize dryer. Green power on light will illuminate.B. Program monitor.1. Language selection:A choice of 5 languages (English, Spa
6D. Operating check points1. Check that green Power-on light is illuminated2. Check that green Compressor-on light is illuminatedif dryer is on in the
7COOLING MEDIUM*AMBIENTTEMPERATURE MULTIPLIER°F °C80 27 1.1290 32 1.06100 38 1.00110 43 0.94INLET COMPRESSED AIR CONDITIONSINLETINLET TEMPERATURESPRES
8ENGINEERING DATAMINIMUM - MAXIMUM OPERATING CONDITIONSMin.-Max. Inlet Air Pressure (compressed air at inlet to dryer) 30-20
9DIMENSIONS / WEIGHTSDimensionsinchesModel 200-300 400-500 750A 40-1/8 52-1/8 57-7/16B48 5165C 21-3/4 27-1/2 27-1/2D 2-3/4 5 5E8 9 9F 2-13/16 3-1/4 3-